Cable construction:
- Conductor - DIN VDE 0295; IEC 60228;EN 60228 CI 5 Stranded Electrolytic Tinned Copper;
- Insulation - Halogen Free Special Copolymer;
- Outer Sheath - Halogen Free Special Copolymer.
Cable dimensions:
- Nominal cross sec. - 4.00 mm2
- Cable diameter - 5.5 mm
- Copper weight - 34 kg/km
- Cable weight - 62 kg/km
Current carrying capacity of PV cables in accordance to the installation (T=40° C)
- Single cable free in air - 55A
- Single cables on surfaces - 52A
- Cables adjusted on surfaces - 44A
Additional parameters for Solar cables:
- Conductor Resistance - 5.09 om/km
- Bending Min. Diameter - 5 x Cable diameter
- Test Voltage - 6,5 kV AC
- Maximum permitted voltage - 1,8 kV DC
- Nominal Voltage Uo /U - 1.0/1.0 kV AC; 1.5/1.5 kV DC
- Working Temperature - from -40°C to +90°C
- Max. conductor temperature - +120°C (for 20.000 hrs.)
Standards:
- Smoke Density Test - IEC 61034-2, VDE 0482-1034-2, EN 61034-2
- Flame Retardant Test - IEC 60332-1-2, VDE 0482-332-1-2, EN 60332-1-2
- Corr. of Combustion Gasses - IEC 60754-2, VDE 0482-754-2, EN 60754-2
- Halogen Free Test - IEC 60754-1, VDE 0482-754-1, EN 60754-1
- Flame Propagation Test - IEC 60332-3-24, VDE 0482-332-3-24, EN IEC 60332-3-24
Weight, kg | 0.000000 |
---|---|
Brand | Conneu |
Color | Red |
Country of Manufacture | Türkiye |
Number of cores | 1 |
Nominal cross section conductor, mm2 | 4.00 |
Depth, cm | 0.000000 |
Width, cm | 0.000000 |
Height, cm | 0.000000 |
Write Your Own Review